High Voltage Metal-Clad Switchgear
• Reliable interlock device
• Double bending process
• Pressure release plates of three high-pressure chambers
• Interchangeability of circuit breaker and handcart
 
            | Item | Unit | Data | |
| Rated Voltage | kV | 12 | |
| 1 min power frequency withstand voltage | Phase to ground, phase to phase | kV | 42 | 
| Between contacts | kV | 48 | |
| Lighting impulse withstand voltage(peak) | Phase to ground, phase to phase | kV | 75 | 
| Between contacts | kV | 85 | |
| Partial frequency | Hz | 20 | |
| Rated Current | A | 630,1250,1600,2500,3150,4000 | |
| Rated peak withstand current | kV | 40,50,63,80,100,125 | |
| Rated short-circuit withstand current | kV | 16,20,25,31.5,40,50 | |
| Rated short-circuit duration | s | 4 | |
| Rated short-circuit breaking current | kA | 16,20,25,31.5,40,50 | |
| Rated short-circuit making current (peak) | kA | 40,50,63,80,100,125 | |
| Protection level | Enclosure:IP4X | ||
| Circuit breaker door open: IP2X | |||
| Weight | kg | 700~1200 | |
| Length*depth*height | mm | 800(1000)*1500*2300 | |