High Voltage AC Automatic Recloser
•Remote signaling function: Accurately collect switch status information;
•Telemetry function: collect switch AC analog data information;
•Remote control function: support the remote control function of the remote master station;
•Overcurrent protection: with a definite time limit and inverse time limit overcurrent protection function;
•Grounding protection: It has the function of researching and judging small current grounding protection of different neutral point grounding systems;
•Reclosing function: parameters such as reclosing times and interval times can be set according to the user's needs to realize the reclosing function.
Item | Unit | Data | ||
| Rated voltage | kV | 27 | ||
| Rated current | A | 630 | ||
| Rated frequency | Hz | 50/60 | ||
| Rated short-circuit breaking current | kA | 12.5 | ||
| Rated short-circuit making current (peak value) | kA | 32.5 | ||
| Rated short-time withstand current | kA | 12.5 | ||
| Rated power frequency withstand voltage (phase-to-phase/to-ground) | kV | 60 | ||
| Rated lightning impulse withstand voltage (phase-to-phase/to-ground) | kV | 125 | ||
| Nominal operating sequence | O-0. 5 s-CO- 2s- CO- 5 s-CO -Latch | |||
| Rated short circuit duration | Second-rate | 3 | ||
Mechanical life | - 40 ℃ to + 70 ℃ | 10000 _ | ||
| Degree of protection | IP65 | |||