2500kW
•Three-level topology, maximum efficiency 99%
•Four quadrant operation, with battery charge and discharge management function
•High protection level (IP54, C5 optional)
•DC side 250kA short-circuit current breaking capacity
•It has the functions of primary frequency modulation and fast dispatching of source network load
System type | 2500kW |
DC Side Data | |
DC voltage range | 580~850V |
Maximum DC current | 1220A*4 |
AC Side Data | |
AC side rated power | 630kW*4 |
AC side maximum power | 693kVA*4 |
Rated AC current | 1010A*4 |
Maximum AC current | 1111A*4 |
Rated AC voltage | 400Vac,3W+PE |
AC voltage range | 400Vac,(-15%~+10%) |
Max.THD of current | <3%(at nominal power) |
DC component | <0.5%(at nominal power) |
Power factor | >0.99 |
Adjustable power factor | 1 leading ~ 1 lagging |
Nominal grid frequency | 50/60 Hz |
Grid frequency range | ±5Hz |
Isolation method | Transformer Isolation |
Transformer Data | |
Rated power | 2500kVA |
Maximum power | 2750kVA |
Voltage ratio | 0.55kV/6~35kV |
Bank type | Dy11 |
General Data | |
Dimensions of unit (W * H * D) | 6058×2896×2438mm |
Weight of unit | 15T |
Degree of protection | IP54 / NEMA 3R |
Operating temperature range | -30 ~+60°C(>50°C derating) |
Operating humidity range | 0-95%(non-condensing) |
Max. working altitude | 3000m |
Cooling concept of PCS chamber | Temperature controlled forced air cooling |
Communication interfaces | RS485 / CAN 2.0 / Ethernet |
Communication protocols | General:Modbus RTU,Modbus TCP,IEC 104 |
Optional:IEC 61850 | |
Compliance | CE,IEC 61000,IEC 62477-1:2012,IEC 61727,IEC 62116 |