1.7MW/3.7MWh
• Highly integrated system with separate inverter and battery sections to allow flexible transportation and on-site installation.
• Higher energy density system with advanced battery, higher efficiency and longer cycle life.
• Integrated with the local controller, HVAC and FSS to enable unified communication, ensure system safety and maximize system efficiency.
System type | WBS-3727K-A02 |
Battery Data | |
Cell type | Lithium iron phosphate battery 3.2V/280Ah |
Configuration of system | 416S10P |
Battery capacity(BOL) | 3727 kWh |
Battery voltage range | 1123 ~ 1498V |
BMS communication interfaces | RS485, Ethernet |
BMS communication protocols | Modbus RTU, Modbus TCP |
AC Data | |
Nominal AC power | 1725kVA |
Max. AC power | 1900kVA |
Max.THD of current | < 3% (at nominal power) |
DC component | < 0.5% (at nominal power) |
Nominal grid voltage | 10kV/35 kV |
Power factor | > 0.99 (at nominal power) |
Adjustable power factor | 1 leading ~ 1 lagging |
Nominal grid frequency | 50/60 Hz |
Grid frequency range | ±5Hz |
Isolation method | Transformer Isolation |
Nominal output voltage of off-grid | 10kV/35 kV ±7% |
Max.THD of off-grid output voltage | < 3% (linear load) |
General Data | |
Dimensions of PCS unit (W * H * D) | 6,058 * 2,896 * 2,438 mm |
Dimensions of battery unit (W * H * D) | 12,192 * 2,896 * 2,438 mm |
Weight of PCS unit | 16 T |
Weight of battery unit (with / without battery) | 40 T |
Degree of protection | IP54 / NEMA 3R |
Operating temperature range | -20 to 55 °C |
Relative humidity | 0 ~ 95 % (non-condensing) |
Max. working altitude | 3000m |
Cooling concept of battery chamber | Heating, Ventilation and Air Conditioning |
Cooling concept of PCS chamber PCS | Temperature controlled forced air cooling |
Fire suppression system of battery unit | Heptafluoropropane/Perfluorohexanone |
Communication interfaces | RS485, Ethernet |
Communication protocols | Modbus RTU, Modbus TCP, IEC 104 |
Compliance | UL 9540, UL 9540A UN38.3 IEC 62619 |